VPT75M
- Suitable for three phase supplies using current transformers (1A or 5A secondary)
- Accuracy Class 0.5S
- DIN72
- Touch key design for easy setup and viewing of measurements
- Supports bi-directional measurement of active and reactive energy
- Multi-function parameter measurement for voltage, current, active power, reactive power, apparent power and power factor
- Offers RS485 Modbus communication
Contact
Tell a friend
Complete the form below and we'll send details of this product to your friend
The VPT75M compact panel mount energy meter, supports three phase and single phase loads using current transformers with a 1A or 5A secondary. This highly accurate meter, class 0.5S, measures bi-directional energy, voltage, current, active power, reactive power, apparent power and power factor.
It provides an RS485 communication interface supporting Modbus and features a clear LCD screen. The touch key allows easy viewing of parameters and setup operations while the password protection function ensures data security.
Electrical Characteristics
| Supply voltage | 100 to 420 V DC |
| Power consumption | <4VA/0.5W |
| Rated voltage (Un) | 230/400V AC |
| Operational voltage | L-N: 30 to 350V AC L-L: 30 to 660V AC |
| PT1 (Primary) | 30 – 500,000V |
| Impedance of voltage measurement circuit | 1MΩ |
| Overload capacity of voltage | 2 x Un for 1 second |
| Rate current(lb) I | 5A |
| Maximum current (lmax) | 6A |
| Minimum current (lmin) | 0.05A |
| CT1 (Primary) | 1 – 9999A |
| Impedance of current measurement circuit | <0.01MΩ |
| Overload capacity of current | 20 x Imax for 0.5 second |
| Operational frequency range | 45 - 65Hz |
| Pulse constant | 5000 imp/kWh |
| Display | LCD with backlight |
| Maximum reading of energy | 9999999.9 kWh/kVArh |
| Measurement type | 3P4W, 3P3W, 2P3W, 1P2W |
Measurement Accuracy
| Voltage, Current | ±0.5% |
| Active power | 0.5% |
| Reactive power | ±2.0% |
| Apparent power | ±1.0% |
| Active energy | ±0.5% |
| Reactive energy | ±2.0% |
| Power factor | ±1.0% |
| Frequency | ±0.2% |
Environmental Characteristics
| Operating Temperature | -25 to +55°C |
| Storage Temperature | -40 to +80°C |
| Humidity | < 90%, non-condensing |
| Pollution Degree | 2 |
| Altitude | Up to 2000m |
| Vibration | 10 Hz to 150Hz, IEC 60068-2-6 |
| IP Degree of Protection | IP51 front display IP30 meter body |
Electromagnetic Characteristics
| Electrostatic Discharge | ±8kV (contact discharge) / ±15kV (air discharge) |
| Immunity to Radiated Fields | 10V/m, 80 - 2000MHz |
| Immunity to Electrical Fast Transients | ±4kV |
| Immunity to Surges | ±4kV |
| Immunity to Conducted Disturbances | 10V, 0.15-80MHz |
| Immunity to Magnetic Fields | IEC 61000-4-8 |
| Immunity to Voltage Dips | IEC 61000-4-11 |
| Radiated Emissions | Class B, according EN55011 |
| Conducted Emissions | Class B, according EN55011 |
| Harmonics Emissions | IEC 61000-3-2 |
Safety
| Overvoltage Category | CAT III, according to IEC 61010-1 |
| Measurement Category | CAT III, according to IEC 61010-1 |
| Insulation | AC Voltage Test: 4kV for 1 minute |
| Protective Class | II, according IEC61010-1 |
Communication
| Interfaces standard and protocols | 2-wire RS485, Modbus |
| Baud rate | 1200 to 38400 bps, default is 9600 bps |
| Parity bit | None, Even, Odd, default is None |
| Stop bit | 1 or 2, default is 1 |
| Response time | < 100ms |
| Transmission mode | Half-duplex |
| Transmission distance | Up to 1000m |
| Max. Bus loading | 64 pc |