VDT45M

  • Suitable for three phase supplies using CT’s (1A or 5A secondary)
  • MID Approved
  • Accuracy Class C (±0.5%)
  • 4 module width, DIN rail installation
  • Touch key design for easy setup and viewing of measurements
  • Supports bi-directional measurement of active and reactive energy
  • Multi-function parameter measurement for voltage, current, active power, reactive power, apparent power and power factor
  • Offers RS485 Modbus communication and one passive pulse output

Contact

I'm interested in...

Tell a friend

Complete the form below and we'll send details of this product to your friend

The VDT45M energy meter supports three phase and single phase loads using current transformers with a 1A or 5A secondary. This MID Approved meter can be used for billing applications and is highly accurate, class C (Cl. 0.5). It measures bi-directional energy, voltage, current, active power, reactive power, apparent power and power factor.

It provides an RS485 communication interface supporting Modbus and features a clear LCD screen. The touch key allows easy viewing of parameters and setup operations while the password protection function ensures data security.

Electrical Characteristics
Supply voltage120 to 420 V DC
Power consumption <4VA/0.5W
Rated voltage (Un)230/400V AC
Operational voltageL-N: 30 to 350V AC
L-L: 30 to 500V AC
PT1 (Primary)30 – 500,000V
Impedance of voltage measurement circuit1MΩ
Overload capacity of voltage2 x Un for 1 second
Rate current(lb) I5A
Maximum current (lmax)6A
Minimum current (lmin)0.05A
CT1 (Primary)1 – 9999A
Impedance of current measurement circuit<0.01MΩ
Overload capacity of current20 x Imax for 0.5 second
Operational frequency range45 - 65Hz
Pulse constant5000 imp/kWh
DisplayLCD with backlight
Maximum reading of energy9999999.9 kWh/kVArh
Measurement type3P4W, 3P3W, 1P2W
Measurement Accuracy
Voltage, Current±0.5%
Active power0.5%
Reactive power±2.0%
Apparent power±0.5%
Active energy±0.5%
Reactive energy±2.0%
Power factor±0.5%
Frequency±0.1%
Environmental Characteristics
Operating Temperature-25 to +55°C
Storage Temperature-40 to +80°C
Humidity< 90%, non-condensing
Pollution Degree2
AltitudeUp to 2000m
Vibration10 Hz to 150Hz, IEC 60068-2-6
IP Degree of ProtectionIP51 front display
IP30 meter body
Electromagnetic Characteristics
Electrostatic Discharge±8kV (contact discharge) / ±15kV (air discharge)
Immunity to Radiated Fields10V/m, 80 - 2000MHz
Immunity to Electrical Fast Transients±4kV
Immunity to Surges±4kV
Immunity to Conducted Disturbances10V, 0.15-80MHz
Immunity to Magnetic FieldsIEC 61000-4-8
Immunity to Voltage DipsIEC 61000-4-11
Radiated EmissionsClass B, according EN55011
Conducted EmissionsClass B, according EN55011
Harmonics EmissionsIEC 61000-3-2
Safety
Overvoltage CategoryCAT III, according to IEC 61010-1
Measurement CategoryCAT III, according to IEC 61010-1
InsulationAC Voltage Test: 4kV for 1 minute
Protective ClassII, according IEC61010-1
Communication
Interfaces standard and protocols2-wire RS485, Modbus
Baud rate1200 to 38400 bps, default is 9600 bps
Parity bitNone, Even, Odd, default is None
Stop bit1 or 2, default is 1
Response time< 100ms
Transmission modeHalf-duplex
Transmission distanceUp to 1000m
Max. Bus loading64 pc
Pulse Output
Interface typeOpen collector opto-coupler
Pulse constantPer pulse equal 0.001 / 0.01 / 0.1 / 1 kWh/kVArh
Pulse width60 / 100 / 200 milliseconds
Pulse output typeActive energy / Reactive energy (Tot, Imp & Exp)
ClassClass A, according to IEC 62053-31
Input voltage5 to 27 VDC