VDT41M

  • Suitable for three phase supplies up to 100A
  • MID Approved
  • Accuracy Class C (±0.5%)
  • 4 module width, DIN rail installation
  • Touch key design for easy setup and viewing of measurements
  • Supports bi-directional measurement of active and reactive energy
  • Multi-function parameter measurement for voltage, current, active power, reactive power, apparent power and power factor
  • Offers RS485 Modbus communication and one passive pulse output

Contact

I'm interested in...

Tell a friend

Complete the form below and we'll send details of this product to your friend

The VDT41M energy meter supports three phase and single phase direct connect loads up to 100A. This MID Approved meter can be used for billing applications and is highly accurate, class C (Cl. 0.5). It measures bi-directional energy, voltage, current, active power, reactive power, apparent power and power factor.

It provides an RS485 communication interface supporting Modbus and features a clear LCD screen. The touch key allows easy viewing of parameters and setup operations while the password protection function ensures data security.

Electrical Characteristics
Rated voltage (Un)230/400V AC
Operational voltageL-N: 85 to 275V AC; L-L: 85 to 480V AC
Overload capacity of voltage2 x Un for 1 second
Rate current(lb) I5A
Maximum current (lmax)100A
Minimum current (lmin)0.25A
Overload capacity of current30 x Imax for 0.01 second
Operational frequency range45 - 65Hz
Power consumption<2W/10VA
Pulse constant400 imp/kWh
DisplayLCD with backlight
Maximum reading of energy9999999.9 kWh/kVArh
Measurement type3P4W, 3P3W, 1P2W
Measurement Accuracy
Voltage, Current±0.5%
Active power±1.0%
Reactive power±2.0%
Apparent power±1.0%
Active energy±0.5%
Reactive energy±2.0%
Power factor±1.0%
Frequency±0.2%
Environmental Characteristics
Operating Temperature-25 to +55°C
Storage Temperature-40 to +80°C
Humidity< 90%, non-condensing
Pollution Degree2
AltitudeUp to 2000m
Vibration10 Hz to 150Hz, IEC 60068-2-6
IP Degree of ProtectionIP51 front display
IP30 meter body
Electromagnetic Characteristics
Electrostatic Discharge±8kV (contact discharge) / ±15kV (air discharge)
Immunity to Radiated Fields10V/m, 80 - 2000MHz
Immunity to Electrical Fast Transients±4kV
Immunity to Surges±4kV
Immunity to Conducted Disturbances10V, 0.15-80MHz
Immunity to Magnetic FieldsIEC 61000-4-8
Immunity to Voltage DipsIEC 61000-4-11
Radiated EmissionsClass B, according EN55011
Conducted EmissionsClass B, according EN55011
Harmonics EmissionsIEC 61000-3-2
Safety
Overvoltage CategoryCAT III, according to IEC 61010-1
Measurement CategoryCAT III, according to IEC 61010-1
InsulationAC Voltage Test: 4kV for 1 minute
Protective ClassII, according IEC61010-1
Communication
Interfaces standard and protocols2-wire RS485, Modbus
Baud rate1200 to 38400 bps, default is 9600 bps
Parity bitNone, Even, Odd, default is None
Stop bit1 or 2, default is 1
Response time< 100ms
Transmission modeHalf-duplex
Transmission distanceUp to 1000m
Max. Bus loading64 pc
Pulse Output
Interface typeOpen collector opto-coupler
Pulse constantPer pulse equal 0.001 / 0.01 / 0.1 / 1 kWh/kVArh
Pulse width60 / 100 / 200 milliseconds
Pulse output typeActive energy / Reactive energy (Tot, Imp & Exp)
ClassClass A, according to IEC 62053-31
Input voltage5 to 27 VDC